Additional system components

Note
The components described here are used in several units in the SINAMICS family. The next
chapter may, therefore, contain references to manuals for these units.
The SINAMICS DC MASTER supports the following components from the SINAMICS drive
system:
CBE20
SMC10, SMC30
TM15
TM31
TM150
In order to operate the SINAMICS DC MASTER with these components, it must be equipped
with (an) Advanced CUD(s); (see the list of options in Chapter "Ordering information for
options and accessories (Page 30)").
The Communication Board CBE20 can be ordered as an option for the SINAMICS DC
MASTER and is installed directly in the unit (in the OMI (Option Module Interface) slot of the
CUD).
The SMC10, SMC30, TM15, TM31 and TM150 modules are installed separately and
connected to the SINAMICS DC MASTER via the DRIVE-CLiQ interface.
Note
The modules SMC10, SMC30, TM15, TM31 and TM150 must not be connected with the
DRIVE-CLiQ hubs DME20 and DMC20 during operation with SINAMICS DCM.

DRIVE-CLiQ interface

On the SINAMICS DC MASTER, up to three terminal modules TM15/TM31/TM150 can be
connected to the DRIVE-CLiQ in any desired combination and in addition one Sensor
Module Cabinet-Mounted SMC10 or SMC30 can be connected.
The CUD features two DRIVE-CLiQ ports (X100, X101). Any combination of the modules
can be connected in series or in parallel. The Sensor Modules SMC10 or SMC30 only have
one DRIVE-CLiQ interface and are therefore always the last module on the bus.
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
Communication Board Ethernet
Sensor Module Cabinet-Mounted
Terminal Module
Terminal Module
Terminal Module
7