Descriptions of functions
10.34 Diagnostics
Parameterizing and operating the function generator
You operate and parameterize the function generator via STARTER.
Figure 10-92 Function generator
Note
Please refer to the online help for more information about parameterization and operation.
Note
The "Function generator as commissioning tool" button must not be selected!
If this button is still selected, then the message "Error occurred while parameterizing" is
output on STARTER when "Loading the parameterization to the drive" as well as alarm
A02007 on the SINAMICS DCM (Function generator: Drive not SERVO/VECTOR).
640
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A