Siemens SINAMICS Series Operating Instructions Manual page 176

Hide thumbs Also See for SINAMICS Series:
Table of Contents

Advertisement

Connecting
6.9 Assignment of terminals and connectors
With option L05
Table 6- 30
Terminal type, electronic power supply
Type
Connection capacity
Stripped length
Tightening torque
Table 6- 31
Assignment of terminals for the electronic power supply
Terminal
Function
XP24V
+
24 V infeed
-
"Power interface with DC electronic power supply" module
6.9.4
Fan
Table 6- 32
Terminal type, fan connections for devices ≥ 400 A with forced ventilation
Type
Connection capacity
The connecting leads must be insulated up to the point where they meet the terminal
enclosure.
Table 6- 33
Terminal assignment for fan connection
Terminal
Function
4U1
400 to 460 V
4V1
infeed
4W1
Protective conductor PE
or
4U1
230 V infeed
4N1
Protective conductor PE
174
MSTB 2.5/CIF plug-in terminal
Rigid/flexible/conductor sizes (mm
Flexible with end sleeve with/without plastic sleeve: 0.25 - 2.5 / 0.25 - 2.5 mm
7 mm
0.5 - 0.6 Nm
Technical specifications
18 V to 30 V DC; current consumption 1 A ... 5 A
Recommended conductor cross-section 1.5 mm
Internal protection with F200 fuses (6.3 A, time-lag),
External protection 6 A ... 16 A, B or C characteristic
DFK-PC4 plug-in terminal
Rigid/flexible/conductor sizes (mm
Technical specifications
3-ph. 400 to 460 V AC with phase sequence L1; L2; L3 (clockwise
phase sequence)
For additional data, refer to the "Technical data" Chapter
230 V 1 AC
for additional data, refer to the "Technical data" Chapter
/mm
/AWG): 0.2 - 2.5 / 0.2 - 2.5 / 24 - 12
2
2
/mm
/AWG): 0.2 - 4 / 0.2 - 4 / 24 - 10
2
2
Operating Instructions, 12/2018, A5E34763375A
2
2
SINAMICS DCM DC Converter