7.3 Interface description
7.3.3.2

X126 PROFIBUS/USS interface

Table 7- 5
Type: 9-way Sub-D socket
NOTICE
Destruction of the CU305 DP when a CAN cable is connected
When a CAN cable is connected to the X126 interface, the CU305 DP or other CAN bus
node can be irreparably damaged.
• Do not connect any CAN cable to the X126 interface.
Communication with USS protocol via RS485
Interface X126 can also be used for communication with USS involving up to 32 nodes. The
STARTER software is used to change the PROFIBUS factory setting to USS. For operation
as a USS interface, only terminals 3, 5, and 8 are used.
You will find information on configuration in the SINAMICS S110 Function Manual.
7.3.3.3

PROFIBUS/USS address switch

With the CU305 DP, the address switch can be used to set both PROFIBUS addresses and
USS addresses. Operation via USS is only possible if the factory setting in the STARTER of
PROFIBUS is changed to USS.
The factory setting for the address switch is 0 or 127. The address switch is located behind
the blanking plate. The blanking plate is part of the scope of supply.
136
X126 PROFIBUS/USS interface
Pin
Signal name
1
Reserved, do not use
2
M
3
1RS_DP
4
1RTS_DP
5
1M
6
1P5
7
P24_SERV
8
1XRS_DP
9
Reserved, do not use
Technical data
Ground to P24_SERV
RS485 differential signal
Request To Send
Ground to 1P5
5 V power supply for bus terminal, exter-
nal, short circuit-proof
24 V for teleservice, short circuit-proof,
150 mA max.
RS485 differential signal
Manual, 07/2015, 6SL3097-4AC10-0BP5