Menu "Pargen" (3+6), Parameters Generator - SMA Sunny Island SI3300 Installation & Operating Instructions Manual

Bidirectional battery inverter for stand-alone applications
Table of Contents

Advertisement

Sunny Island
"PARBAT" (3+5)
Name
Description
every four hours.
536_Fan on del
0 ... 1440 min:
In order to use this setting, "511_Bat Fan" must be set to "Installed"
537_Fan off del
0 ... 360 min:
In order to use this setting, "511_Bat Fan" must be set to "Installed"
538_loss nom
Specific leakage current of battery during float charge at 20 °C
100 ... 0 mA per 100 Ah
Approximate values:
30 mA/100 Ah
80 mA/100 Ah
This value is NOT automatically determined by the Sunny Island. Battery man-
agement can therefore be optimized by manually adjusting the value from time
to time.

8.6 Menu "PARGEN" (3+6), Parameters Generator

This menu can only be selected after the installer password (level: 1) has been
entered.
In the menu "PARGEN" (3+6) the operator can change the parameters for a con-
nected generator. Under the parameter "602_GenSet Type" the type of starting pro-
cedure can be defined. The Sunny Island provides three different starting procedures
(see Fig. 16.1). The individual time periods within these procedures can also be set
in the menu "PARGEN" (3+6).
BWRI33-12:EE
ON delay for battery room fan
OFF delay for battery room fan
for new batteries
for batteries strongly aged
Table 8.3: Settings in menu "PARBAT" (3+5)
Installation & Operating Instructions
- 84 -
SMA Regelsysteme GmbH