SMA Sunny Island SI3300 Installation & Operating Instructions Manual page 131

Bidirectional battery inverter for stand-alone applications
Table of Contents

Advertisement

Sunny Island
„PARALL" (3+9)
Parameter
Unit Min. Max.
310_Auto Start
312_COM1 Proto
313_COM1 Baud
316_COM2 Proto
317_COM2 Baud
BWRI33-12:EE
Default
Description
0
255
0
Number of autostart attempts (0: autostart off)
within one hour. After one hour of operation the
counter will be reset.
Autostart means that approx. 10 sec after a switch-
off (due to error or the like) the Sunny Island re-
starts.
In addition, the Sunny Island starts automatically
after switching on the DC voltage when the
Autostart is activated.
ATTENTION!
The Sunny Island's low battery load mode is not
affected by this setting. Running in that mode it is
thus possible that the Sunny Island will start from
time to time, even if this parameter is set to 0! (s.
Parameter "535_State Stop T" for details)
0
2
1
Communication protocol COM1:
0: None:
1: SMANET:
2: SUNNYNET: interface based on SunnyNet
For communication to Sunny Boys: set to
SUNNYNET
0
9
6
Baud rate COM1 (bits/s)
2: 1200
5: 9600
6: 19200
For communication to Sunny Boys or Sunny Boy
Controls: set to 1200
In three-phase operation all inverters have to be
set to 19200!
0
2
2
Communication protocol COM2:
0: None:
1: SMANET:
2: SUNNYNET: interface based on SunnyNet
For communication to Sunny Boys: set to
SUNNYNET
0
9
2
Baud rate COM2 (bits/s)
2: 1200
5: 9600
6: 19200
For communication to Sunny Boys or Sunny Boy
Controls: set to 1200.
- 131 -
Installation & Operating Instructions
interface not in use
interface based on SMANet
protocol
protocol
interface not in use
interface based on SMANet pro-
tocol
protocol
SMA Regelsysteme GmbH