SMA Sunny Island SI3300 Installation & Operating Instructions Manual page 138

Bidirectional battery inverter for stand-alone applications
Table of Contents

Advertisement

Sunny Island
„PARALL" (3+9)
Parameter
Unit Min. Max.
607_Igen max
610_tGen glow
611_tGen crank
612_tGen warm
613_tGen minrun
min
614_tGen cool
615_tGen stop
616_tGen lock
min
617_tGen fail
min
618_tGen faillock
625_PldL GenOn
%
626_PldL GenOff
%
627_PldS GenOn
%
BWRI33-12:EE
Default
A
0
500
0
s
1
180
15
s
1
60
10
s
1
900
15
1
180
5
s
0
900
60
s
1
180
10
1
180
5
1
180
5
h
1
168
6
-100
100
0
-100
100
0
-100
100
0
Installation & Operating Instructions
Description
Max. generator current (per phase),
only applies if "604_GenSet Ctrl" is set accordingly
Length of time the relay is controlled to glow up the
generator
Length of time the relay is controlled to crank the
generator
Warm-up time of generator
Minimum run time of generator
Cooling time of generator
Length of time the relay is controlled to stop the
generator
Period of time the generator – after having been
stopped - cannot be restarted via the Sunny Island
(can be shortened by confirmation in the
"GENSET" (2-2) menu)
Period of time the generator cannot be restarted
via the Sunny Island after a generator failure (can
be shortened by confirmation in the "GENSET" (2-
2) menu)
Period of time the generator cannot be restarted
via the Sunny Island after a certain number of fail-
ures as defined in "605_GenStRetr" has occurred
during start-up (can be shortened by confirmation
in the "GENSET" (2-2) menu)
Switch-on threshold in % of the nominal power at
one phase for the power-related generator start or
the power-related relais (only K5 or K6). If the re-
lays shall be switched in relation to the power, the
parameters "705_Man K5" and/or "706_Man K6"
must bei set to "LOAD"
Switch-off threshold in % of the nominal power at
one phase for the power-related generator start or
the power-related relais (only K5 or K6). If the re-
lays shall be switched in relation to the power, the
parameters "705_Man K5" and/or "706_Man K6"
must bei set to "LOAD"
Switch-on threshold in % of the nominal power
based on the cumulative power within the three-
phase system for the power-related generator start
or the power-related relays (only K5 or K6). If the
relays shall be switched in relation to the power,
the parameters "705_Man K5" and/or "706_Man
K6" must bei set to "LOAD"
- 138 -