SMA Sunny Island SI3300 Installation & Operating Instructions Manual page 133

Bidirectional battery inverter for stand-alone applications
Table of Contents

Advertisement

Sunny Island
„PARALL" (3+9)
Parameter
Unit Min. Max.
501_Cbat nom
Ah
502_Bat Type
503_Ubat nom
504_Ubat min
505_Ubat max
506_acid density
kg/l
507_SOC ini
%
508_Tbat Sense
509_Tbat max
degC 30
511_Bat Fan
512_Acid Pump
BWRI33-12:EE
Default
100 10000
350
0
2
2
V
54
60
60
V
46
84
51
V
51
84
84
1,1
1,35
1,28
0
100
0
0
1
1
55
40
0
1
0
0
1
0
Installation & Operating Instructions
Description
Nominal battery capacity of 10 hours (C10); always
enter the value stated by the manufacturer even if
the battery has already aged!
Battery type as stated by manufacturer
0: Gel
gel
1: Fleece
fleece
2: Lead-Acid
liquid electrolyte
Nominal battery voltage. Normally 60 V have to be
set. For exceptions see chapter 11.3.
min. battery voltage permissible
max. battery voltage permissible
Nominal acid density according to manufacturer
(only taken into account if inverter is started via
"New System" or "New Battery" (see chapter 6))
Initial discharge degree of battery (only taken into
acount if inverter is started via "New System" or
"New Battery" (see chapter 6))
If set to "0" the Sunny Island estimates the dis-
charge degree based on battery voltage.
Battery temperature sensor installed
0: Not installed
1: Installed
Automatically set to 1 in single-phase systems or
masters in three-phase systems; in all other cases
set to 0.
Can be set to 1 in slaves if temperature sensors
are additionally installed there.
Maximum battery temperature permissible
Battery room fan installed (only for lead-acid bat-
tery with liquid electrolyte)
0: Not installed
1: Installed
Only for lead-acid battery with liquid electrolyte:
0: Not installed
Electrolyte circulation pump not
installed
1: Installed
Electrolyte circulation pump in-
stalled
By selecting "Installed" the electrolyte circulation
pump is switched on depending on settings of pa-
rameters 513 to 516. Irrespective of battery values,
however, there is at least one circulation and 9 cir-
culations maximum per day.
- 133 -