Connection Of The Battery - SMA Sunny Island SI3300 Installation & Operating Instructions Manual

Bidirectional battery inverter for stand-alone applications
Table of Contents

Advertisement

Sunny Island
The required cable cross-section of the grounding conductor can be es-
timated with the following formula for fused interrupters with disconnect-
ing times up to 5 s if a copper cable is used:
(I
SC
S =
143
t = disconnecting time in seconds, I
amperes, S = conductor cross-section in mm²
The maximum battery current can be seen in the data sheets for the bat-
tery. If this is not possible it can usually be estimated with the following
formula:
C
I
=
0,05h
SC
C = battery capacity in Ah
For an exact determination of the grounding conductor cross-section please refer to
the relevant standards (e. g. VDE 0100 part 540).

3.4.2 Connection of the battery

On the DC side a suitable storage battery has to be connected according to DIN
VDE 0510 (VDE specification for electric storage batteries and battery plants).
Make sure the cable to the storage battery has a sufficient cross-
section. Pay attention to the correct polarity of the connection to the
storage battery.
If the battery is to be grounded please follow the special instructions
in chapter 3.4.1.