3.6.2 Assignment of COM2 Interface

The signals listed in Table 3.3 are available when the corresponding Piggy-Back has
been installed.
PIN
RS485 Signal
1
2
Data +
3
Data +
4
5
GND
6
+5V
7
8
Data -
9
Data -
Table 3.3: Assignment of COM2 interface (RS485 / RS232)
Recommended cable for RS485 (COM1 and COM2)
We generally recommend a so-called LICY 2 x 2 x 0.25 mm² cable as shown in Fig.
3.19.
Twisted pair 1 (2 x 0.25 mm)
Fig. 3.19: Recommended cable for RS485 communication
The total length of the RS485 connection cable may not exceed 1200 m.