Communication; Setting The Grid And Country Parameters; Setting The Installation Country - SMA SUNNY MINI CENTRAL 4600A Installation Manual

Pv inverter
Hide thumbs Also See for SUNNY MINI CENTRAL 4600A:
Table of Contents

Advertisement

Electrical Connection
5.6 Communication
The inverter is equipped with a slot for communication interfaces in order to communicate with special
data loggers (e.g., Sunny WebBox) or a PC with corresponding software (e.g., Sunny Data Control
or Sunny Explorer).
Refer to the respective communication interface manual for a detailed wiring diagram and an
installation description for the interface.
The inverter's active power can be limited or its displacement power factor can be set externally using
the Power Reducer Box from SMA Solar Technology AG. Detailed information on the
Power Reducer Box is available in its Technical Description at www.SMA.de/en.
5.7 Setting the Grid and Country Parameters
Changing grid‑relevant and country parameters
To change grid‑relevant parameters, you need a personal access code – the so‑called
SMA Grid Guard Code. The application form for the personal access code is available in
the download area at www.SMA.de/en, in the "Certificate" category of the respective
inverter.
Ensure that you discuss the changes to these parameters with your grid operator.
A detailed description of the operating parameters for the inverter is available in the download area
at www.SMA.de/en in the category "Technical Description" of the respective inverter.
5.7.1 Setting the Installation Country
Using the "Default" parameter, you can set the installation country and/or the grid connection
standard valid for the country via a communication product (e.g., Sunny WebBox) or a PC with
corresponding software (e.g., Sunny Data Control or Sunny Explorer). This, however, is only required
if the inverter was originally ordered for another country. You can see the standard to which the
inverter was set upon delivery on the type label and on the included supplementary sheet with the
default settings.
46
SMC46-60A-IA-IEN120471
SMA Solar Technology AG
Installation Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny mini central 5000aSunny mini central 6000a

Table of Contents