SMA Sunny Island SI3300 Installation & Operating Instructions Manual page 64

Bidirectional battery inverter for stand-alone applications
Table of Contents

Advertisement

Sunny Island
Parameter
Default
602_GenSet
None
type
603_GenSet Inte None
Table 6.1: Parameters to be entered for configuration via "New System"
Lead-acid batteries with a liquid electrolyte are also called non VARLA
while batteries labeled VARLA (VAlve Regulated Lead Acid) or mainte-
nance-free are normally gel or fleece batteries.
BWRI33-12:EE
Installation & Operating Instructions
Description
slave 2
1Phs_Slv3:
single-phase parallel peroration with three de-
vices with one single battery pack, device is
slave 3
3Phs_Mstr1Set: three-phase operation, device is master (L1)
3Phs_Slv1L2:
three-phase operation, device is slave (L2)
3Phs_Slv1L3:
three-phase operation, device is slave (L3)
None:
No generator present in island grid
Grid forming:
Generator forms the grid
Mains:
Sunny Island is operated on public utility grid
BHKW-Mains
Sunny Island is operated together with the
Ecopower CHP and on the public utility grid
BHKW-Island
Sunny Island is operated solely together with
the Ecopower CHP
Mains form
Sunny Island is operated together with a grid-
forming generator and on the public utility grid
fast Grid form
Generator is grid-forming and it is switched be-
tween the generator and the Sunny Island with-
out interruption (special installation measures
are necessary for this)
fast Mains
The Sunny Island is operated on the public util-
ity grid and it is possible to switch from the
Sunny Island as grid-former to the public utility
grid without interruption. (special installation
measures are necessary for this)
fast Mains form The Sunny Island is operated together with a
grid-forming generator and on the public utility
grid. Switching takes place without interruption
(special installation measure are necessary for
this)
0: None:
No generator start via Sunny Island
1: Type 1:
Autostart, relays K1+K2
2: Type 2:
3 contacts Run / Start, relays K1, K2, K5
3: Type 3:
3 contacts Start / Stop, relays K1, K2, K5
4: EcoPower
Ecopower CHP
(see also chapter 16 "Starting phase sequence of different
generator types")