Information On The Motor-Drive Converter Selection, Im Analog - Siemens SIMODRIVE 611 Planning Manual

Drive converter
Hide thumbs Also See for SIMODRIVE 611:
Table of Contents

Advertisement

4 Power Modules
4.2 Current de–rating
4.2.2
4
Table 4-6
PM
Code
type
No.
LT 8A
1
LT 15A
2
LT 25A
3
LT 50A
6
LT 80A
7
LT 108A
13
LT 120A
8
LT 160A
9
LT 200A
10
LT 300A
11
LT 400A
12
4-90
Information on the motor–drive converter selection, IM analog
The converter must be selected according to the required duty cycle.
Further, the following restrictive conditions must be observed:
S
The motor no–load current must be less than the rated current of the drive
converter module (IM according to Table 4-6).
S
As result of the current actual value resolution, the lowest no–load motor
current must fulfill the following condition:
n
FS
n
max
Various inverter clock frequencies can be parameterized; observe the current
de–rating.
Inverter clock frequency IM analog f
In/Is6/Imax
In/Is6/Imax
in A
in A
f
f
T
T
3.20 kHz
4.70 kHz
3/3/3
2.5/2.5/2.5
5/5/8
4.2/4.2/6.8
8/10/16
6.9/8.6/13.8
24/32/32
20/26/26
30/40/51
26/34/44
45/60/76
39/52/65
45/60/76
39/52/65
60/80/102
51/68/86
85/110/127
73/95/109
120/150/193
101/127/163
200/250/257
169/211/217
up to including FW 2.xx
I
Rated module current at the converter pulse frequency
N
(standard value: f
I
Minimum motor current
min
I
Max. motor current for an S6 load duty cycle
S6
I
Short–time limiting current of the module used in A
Short
I
No–load motor current in A
0Mot
n
Speed at the start of field weakening
FS
n
Maximum motor speed
max
S
For motors with a low leakage induction, it may be necessary to provide a
series reactor and/or increase the inverter clock frequency of the drive con-
verter. From experience, motors with low leakage induction are those which
can achieve high stator frequencies (maximum motor stator frequency
300 Hz) or motors with a higher rated current (rated current
w
I
I
(I
0Mot
min
min
=3.2 kHz: Currents as a function of the inverter clock frequency f
0
In/Is6/Imax
In/Is6/Imax
In/Is6/Imax
in A
in A
f
f
T
T
6.30 kHz
7.80 kHz
2.80 kHz
2.0/2.0/2.0
1.6/1.6/1.6
3.4/3.4/5.4
2.6/2.6/4.2
5.7/7.1/11.4
4.6/5.7/9.1
8/10/16
15/20/20
10/14/14
24/32/32
21/28/36
17/23/29
30/40/51
32/43/54
26/34/43
45/60/76
32/43/54
26/34/43
45/60/76
41/54/69
31/42/53
60/80/102
60/78/90
48/63/72
85/110/127
81/102/131
62/78/101
120/150/193
135/169/174
104/130/134
200/250/257
from FW 3.0
3.2 kHz)
0
rms
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
according to Table 4-6)
In/Is6/Imax
In/Is6/Imax
in A
in A
in A
f
f
f
T
T
T
3.90 kHz
5.00 kHz
3/3/3
2.8/2.8/2.8
2.4/2.4/2.4
5/5/8
4.6/4.6/7.4
4.1/4.1/6.5
7.4/9.3/15.0
6.7/8.3/13.3
22/29/29
19/25/25
28/37/48
25/33/42
42/56/71
37/50/63
42/56/71
37/50/63
56/74/95
49/65/83
79/103/119
71/91/106
111/139/179
98/122/157
185/232/238
163/203/209
rms
85 A).
>
 Siemens AG 2001 All rights reserved
05.01
T
In/Is6/Imax
Imin
in A
in A
f
T
5.90 kHz
2.2/2.2/2.2
0.6
3.6/3.6/5.8
1.1
6.0/7.5/12.0
1.8
16/21/21
3.6
22/30/38
5.7
34/45/57
8.5
34/45/57
11.3
43/58/73
11.3
63/82/95
14.1
86/108/139
21.2
144/180/185
28.3
>