Assigning The Line Filters To The I/R Modules - Siemens SIMODRIVE 611 Planning Manual

Drive converter
Hide thumbs Also See for SIMODRIVE 611:
Table of Contents

Advertisement

7 Line Supply Connection
7.2 Line filter and HF commutating reactors for I/R and UI modules
7.2.1
Table 7-9
Filter
components
Order No.
Line filter
Mounting
position
Module width
Filter Filter
I
filter
rated
P
filter
v
Connection
7
Terminals,
Line supply input
Terminals,
output
2)
I
fuse
rated
Cooling
Radio interfe-
rence suppres-
sion
EN 55011
Table 7-10
Filter packages
Contents:
6SN1111–0AA00
6SN1111–0AA01
Mounting position
of the filter
modules
1) The 1st number is valid for cable lugs, the 2nd number is for finely–stranded conductors without connector sleeves.
2) The fuse used must have this rated current. Refer to Table 7-1 for recommended fuses.
7-214

Assigning the line filters to the I/R modules

Assigning the line filters to the I/R modules
I/R module
I/R module
16/21 kW
36/47 kW
Line filter 16 kW
Line filter 36 kW
6SN1111–
6SN1111–
V
0AA01–2BA
0AA01–2CA
Wall or floor mounting, refer to dimension drawings, Section 12.
Refer to the dimension drawings, Section 12.
9 kg
16 kg
30 A
67 A
70 W
90 W
2
1)
16/10 mm
50 mm
PE, (M5)
PE, (M8)
LINE
LINE
L1, L2, L3, PE
L1, L2, L3, PE
LOAD
LOAD
L1, L2, L3
L1, L2, L3
35 A
80 A
Non–ventilated
Non–ventilated
Cable–borne, limit
Cable–borne, limit
value Class A
value Class A
Filter packages
16 kW package
36 kW package
6SN1111–
6SN1111–
0AA01–2BB0
0AA01–2CB0
HF commutating
HF commutating
reactor
reactor
16 kW
36 kW
–0BAV
–0CAV
Line filter 16 kW
Line filter 36 kW
–2BAV
–2CAV
The filter modules can be mounted horizontally and vertically (line at the bottom,
load at the top).
I/R module
55/71 kW
Line filter 55 kW
6SN1111–
V
V
0AA01–2DA
19 kg
103 A
110 W
2
2
50 mm
PE, (M8)
LINE
L1, L2, L3, PE
LOAD
L1, L2, L3
125 A
Non–ventilated
Cable–borne, limit
value Class A
55 kW package
6SN1111–
0AA01–2DB0
HF commutating
reactor
55 kW
–0DAV
Line filter 55 kW
–2DAV
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
05.01
I/R module
I/R module
80/104 kW
120/156 kW
Line filter 80 kW
Line filter 120 kW
6SN1111–
6SN1111–
V
0AA01–2EA
0AA01–2FA
22 kg
32 kg
150 A
225 A
150 W
190 W
2
95 mm
Cable lug acc. to
PE, (M8)
DIN 46235
LINE
LINE
L1, L2, L3, PE
L1, L2, L3, PE
LOAD
LOAD
L1, L2, L3
L1, L2, L3
160 A
250 A
Non–ventilated
Non–ventilated
Cable–borne, limit
Cable–borne, limit
value Class A
value Class A
80 kW package
120 kW package
6SN1111–
6SN1111–
0AA01–2EB0
0AA01–2FB0
HF commutating
HF commutating
reactor
reactor
80 kW
120 kW
–1EAV
–1FAV
Line filter 80 kW
Line filter 120 kW
–2EAV
–2FAV
 Siemens AG 2001 All rights reserved