Technical Data, Line Supply Infeed Modules - Siemens SIMODRIVE 611 Planning Manual

Drive converter
Hide thumbs Also See for SIMODRIVE 611:
Table of Contents

Advertisement

05.01
6.3.1

Technical data, line supply infeed modules

Supply
voltage and
frequency
Table 6-5
Supply voltage and frequency
v 55 kW
NE modules up to P
n
I/R modules Pn = 80/120 kW
Power connection: U1, V1, W1
Coil connection: L1, L2
only for 80 kW and 120 kW
No ground fault
The cabinet wiring, the motor/encoder feeder cables and the DC link connec-
tions should be checked to ensure that there are no ground faults before the
equipment is powered–up for the first time.
Nominal load duty
cycles for
NE modules
P
P
max
P
s6
P
n
4 min
0.4 P
n
10 min
S6 load duty cycle with
pre–loading condition
P
P
max
P
n
0.2 s
10 s
Peak output duty cycle with pre–loading condition
Fig. 6-5
Nominal load duty cycles for NE modules
 Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
S1, S4 = OFF
Vn = 3–ph. 400 V AC
Vn = 3–ph. 415 V AC
3–ph. 360...440 V AC
3–ph. 373...457 V AC
1)
3–ph. 300...360 V AC
3–ph. 312...373 V AC
45...65 Hz
2–ph. 360...457 V AC / 45...53 Hz
2–ph. 400...510 V AC / 57...65 Hz
P
P
max
P
s6
P
n
10 s
0.4 P
n
t
Peak output duty cycle with
pre–loading condition
P
FP
n
P
n
t
Peak output duty cycle without pre–loading condition
F: F=1.6 applies for all NE modules up to Pn  80 kW
F=1.4 applies for Pn=120 kW
6 Infeed Modules
6.3 Technical data
S1 = ON
S4 = ON
Vn = 3–ph. 480 V AC
3–ph. 432...509 V AC
1)
3–ph. 408...432 V AC
45...65 Hz
55...65 Hz
t
60 s
4 s
t
10 s
1)
6
6-173