General
Switch S1 is provided on the upper side of the NE and monitoring module to set
information
the following functions (for 5 kW UI at the front panel):
Fig. 6-4
Note
For a configuration for 480 V (S1.4= ON), the regenerative feedback is closed–
loop controlled. The setting of S1.5 is of no importance.
Notice
For I/R modules, Order number: 6SN114V–1VV0V–0VV1 Sinusoidal
operation is the basic setting.
For operation with filters, which are not listed in Table 6-1 the system must be
changed–over to squarewave current operation, in order that the filter is not
thermally overloaded.
Terminal 63 (pulse enable) and/or terminal 48 (start terminal, contactor control)
must be de–energized before the system is powered–up or powered–down
using the main switch or a line contactor!
Switch S1.1
OFF: I/R module,
ON:
PR = Pulsed resistor
1)
only possible for the I/R module, monitoring thresholds are increased for all NE modules.
 Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
ON:
1)
V
= 415 V"10 % V
= 625 V
supply
DC link
Fault message
Regenerative feedback off
+
V
= 480 V
6 %–10 %
supply
Controlled infeed off

Sinusoidal current operation
( on the line current side )
Standard setting
DIL switch S1
V
supply
UI module
V
supply
Monitoring thresholds: (I/R, UI, monitoring modules)
PW on = 644 V; PW off = 618 V
U
>> = 695 V
DC link
I/R module
V
supply
UI module
V
supply
Monitoring thresholds: (I/R, UI, monitoring modules)
PW on = 670 V; PW off = 640 V
V
>> = 710 V
DC link
6 Infeed Modules
6.1 Function overview and settings
S1
OFF:
1
V
= 400 V"10 % V
supply
2
Ready signal
3
Regenerative feedback on
4
Standard, refer to switch S1.1
5
Controlled infeed
Square–wave current operation
6
( on the line current side )
3–ph. 400 V AC
3–ph. 415 V AC
ON 1
ON 1
.
.
S1.1
.
.
S1.4
4
4
"
= 400 V
10 %; V
= 600 V
DC link
"
= 400 V
10 %; V
= V
DC link
"
= 415 V
10 %; V
= 625 V
DC link
"
= 415 V
10 %; V
= U
DC link
1)
= 600 V
DC link
3–ph. 480 V AC
ON 1
.
.
4
1.35
supply
1.35
supply
6-165