Configure The Number Of Decimal Places (Precision) Shown On The Display - Emerson Micro Motion 2700 Configuration And Use Manual

With foundation fieldbus
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

Display variable
Display Variable 12
Display Variable 13
Display Variable 14
Display Variable 15
5.1.3
Configure the number of decimal places (precision)
shown on the display
Display
ProLink III
Field Communicator Configure > Manual Setup > Display > Decimal Places
Fieldbus host
Overview
You can specify the number of decimal places (precision) that are shown on the display for
each process variable or diagnostic variable. You can set the precision independently for
each variable.
The display precision does not affect the actual value of the variable or the value used in
calculations.
Procedure
1.
2.
Configuration and Use Manual
Not available
Device Tools > Configuration > Transmitter Display > Display Variables
LDO TB > FBUS_UI_ProcVarIndex (OD Index 40)
LDO TB > UI_NumDecimals (OD Index 41)
Select a variable.
Set Number of Decimal Places to the number of decimal places you want shown
when the process variable or diagnostic variable appears on the display.
For temperature and density process variables, the default value is 2 decimal places.
For all other variables, the default value is 4 decimal places. The range is 0 to 5.
Tip
The lower the precision, the greater the change must be for it to be reflected on the display.
Do not set the precision too low or too high to be useful.
Configure device options and preferences
Process variable assignment
None
None
None
None
57