Configure process measurement
Unit description
Degrees Celsius
Degrees Fahrenheit
Degrees Rankine
Kelvin
4.6.2

Configure Temperature Damping

Display
ProLink III
Field Communicator Configure > Manual Setup > Measurements > Temperature > Temp Damping
Fieldbus host
Overview
Temperature Damping controls the amount of damping that will be applied to the line
temperature value, when the on-board temperature data is used (RTD).
Damping is used to smooth out small, rapid fluctuations in process measurement.
Damping Value specifies the time period (in seconds) over which the transmitter will
spread changes in the process variable. At the end of the interval, the internal value will
reflect 63% of the change in the actual measured value.
Tip
Temperature Damping affects all process variables, compensations, and corrections that use
temperature data from the sensor.
Procedure
Enter the value you want to use for Temperature Damping.
The default value is 4.8 seconds. The range is 0.0 to 38.4 seconds.
Tips
A high damping value makes the process variable appear smoother because the reported value
changes slowly.
A low damping value makes the process variable appear more erratic because the reported value
changes more quickly.
Whenever the damping value is non-zero, the reported measurement will lag the actual
measurement because the reported value is being averaged over time.
38
Display
°C
°F
°R
°K
Not available
Device Tools > Configuration > Temperature
Measurement TB > TEMPERATURE_DAMPING (OD Index 33)
Micro Motion Model 2700 Transmitters with FOUNDATION Fieldbus