Configure Temperature Measurement; Configure Temperature Measurement Unit - Emerson Micro Motion 2700 Configuration And Use Manual

With foundation fieldbus
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

Overview
Density Cutoff specifies the lowest density value that will be reported as measured. All
density values below this cutoff will be reported as 0.
Procedure
Set Density Cutoff to the value you want to use.
For most applications, the default setting (0.2 g/cm³) is sufficient. The range is 0.0 g/cm³
to 0.5 g/cm³.
Effect of Density Cutoff on volume measurement
Density Cutoff affects liquid volume measurement. If the density value goes below Density
Cutoff, the volume flow rate is reported as 0. Density Cutoff does not affect gas standard
volume measurement. Gas standard volume values are always calculated from the value
configured for Standard Gas Density or polled value if configured for polled base density.
4.6

Configure temperature measurement

The temperature measurement parameters control how temperature data from the
sensor is reported.
4.6.1

Configure Temperature Measurement Unit

Display
ProLink III
Field Communicator Configure > Manual Setup > Measurements > Temperature > Temperature Unit
Fieldbus host
Overview
Temperature Measurement Unit specifies the unit that will be used for temperature
measurement.
Procedure
Set Temperature Measurement Unit to the option you want to use.
The default setting is Degrees Celsius.
Options for Temperature Measurement Unit
The transmitter provides a standard set of units for Temperature Measurement Unit.
Different communications tools may use different labels for the units.
Configuration and Use Manual
OFF-LINE MAINT > OFF-LINE CONFG > UNITS > TEMP
Device Tools > Configuration > Process Measurement > Temperature
Measurement TB > TEMPERATURE_UNITS (OD Index 21)
Configure process measurement