Introduction to configuration and commissioning
3.5
Place function, transducer, and resource blocks
in OOS mode
Before you modify parameters on the fieldbus function, transducer, and resource blocks,
you must place the blocks in Out of Service (OOS) mode. Before you return the device to
operation, you must place them back in service (Auto mode).
Prerequisites
Before you modify parameters on the fieldbus function blocks, you must place the
function blocks in OOS mode.
Procedure
Option
Display
ProLink III
Field Communicator
Fieldbus host
Postrequisites
Before you return the device to operation, you must place them back in service (Auto
mode).
3.6

Lockout FOUNDATION Fieldbus hosts

If you plan to use a FOUNDATION Fieldbus connection to configure the device, you can
lock out FOUNDATION Fieldbus hosts. If you do this, the FOUNDATION Fieldbus hosts will
be able to read data from the device, but you will not be able to write data to the device.
Restrictions
This feature is available only if you are using the Field Communicator or AMS.
Procedure
Choose Service Tools > Maintenance > Security and Simulation > Write Lock Setup.
14
Description
Not available
Device Tools > Configuration > Communications > Fieldbus
Overview > Mode
(block name) > MODE_BLOCK (OD Index Number 005)