Process Conditions; Temperature Measurement - Emerson Rosemount 5600 Series Reference Manual

Level transmitter non-contacting radar with hart protocol
Hide thumbs Also See for Rosemount 5600 Series:
Table of Contents

Advertisement

Configuration
March 2020
4.6

Process conditions

Describe the conditions in your tank according to the Process Conditions listed below. For best
performance choose only if applicable and not more than two options.
Rapid level changes
Turbulent Surface
Foam
Solid Products
4.7

Temperature measurement

Up to six temperature sensors can be connected to an existing 2210 Display Unit
elements or 1-6 multiple spot elements. All temperature sensors must be of the same type, for example,
the Pt100 or CU90.
Use one of the following temperature measurement conversion methods:
PT100
CU90
User-defined linearization table. The sensor characteristics are specified in a table of corresponding
resistance and temperature values.
User-defined formula. The sensor characteristics are specified in a mathematical formula: R=R
*(1+A*T+B*T
Centigrade and A and B are constants.
Sensor Mounting Level
1-6
Number of Sensors
1,
The Rosemount 2210 Display Unit was discontinued Oct 2018, and is no longer available for ordering.
70
Optimize the transmitter for measurement conditions where the level changes quickly
due to filling and emptying of the tank. A standard configured transmitter is able to track
level changes of up to 4 inch/s (100 mm/s). When the Rapid Level Changes check box is
marked, the transmitter can track level changes of up to 8 inch/s (200 mm/s).
This parameter should be used if the tank shows a turbulent surface. The reason for the
turbulence might be splash loading, agitators, mixers, or boiling product. Normally the
waves in a tank are quite small and cause local rapid level changes. By setting this
parameter the performance of the transmitter will be improved when there are small and
quickly changing amplitudes and levels.
Setting this parameter optimizes the transmitter for conditions with weak and varying
surface echo amplitudes, which are typical for foam.
Setting this parameter optimizes the transmitter for solid products, for example concrete
or grains, which are not transparent for radar signals. For instance, this parameter can be
used when the application is a silo with product buildup.
2
) where R is the resistance at temperature T, R
Enter the level (from the tank bottom) at which each sensor is mounted. The first
sensor should be mounted in the lowest position in the tank, the second above the
first and so on.
Enter the number of temperature sensors connected to the Display Unit. You can
have up to six sensors connected. If you choose zero sensors temperature
measurement is disabled.
Reference Manual
00809-0100-4024, Rev CA
(1)
.You can use 1-3 spot
is the resistance at zero degrees
0
0
Configuration