Section H: Control Circuit Terminal Parameters

H4 Analog Outputs

H4
Analog Outputs
The VS-616PS5 has two analog outputs, for the external monitoring of drive condi-
tions such as output speed, output current, PID feedback and others.
H4-01 Terminal 21 Analog Output Selection
Selects the analog output monitors for terminal 21.
The resolution of terminal 21 is 9 bits plus a sign bit.
H4-02 Terminal 21 Analog Output Gain
Setting Range:
Factory Default:
Sets the terminal 21 output gain for the analog output monitors. To obtain the output
level, multiply the monitor output level % by the gain value set in this parameter, (H4-
02).
78
Setting
1
Speed reference
2
Output Speed (factory default)
3
Inverter output current
5
Motor speed
6
Output voltage
7
DC bus voltage
8
Output power
9
Torque reference (internal)
15
External terminal 13 input voltage
16
External terminal 14 input voltage
17
External terminal 16 input voltage
18
Motor secondary current (Iq)
19
Motor excitation current (Id)
20
Primary Speed after SFS
21
Speed controller ASR input
22
Speed controller ASR output
27
qAxis current control reference
28
dAxis current control reference
29
Voltage limit control output
30
qAxis current control output
31
dAxis current control output
32
Output voltage reference (V
33
Output voltage reference (V
45
External torque reference
46
Torque compensation value
49
Control section software number
50
Speed detection PG counter value
53
PID feedback
±300.0%