Section H: Control Circuit Terminal Parameters
H1 Digital Inputs
• Up/Down Command (settings: Up = "10," Down = "11")
Allows the motor speed to be increased (Up command) or decreased (Down com-
mand) via contact closures. Requires the run command to be applied.
FWD Run
UP Command S5
DOWN Command S6
Upper Limit Speed
Lower Limit Speed
Output Frequency
Frequency Agree Signal
U:
Up (accelerating) status
D:
Down (decelerating) status
H:
Hold (constant speed) status
U1: Up status, with clamping at upper limit speed
D1: Down status, with clamping at lower limit speed
Notes:
1. Be sure to set Speed Reference Selection (B1-01) = "1." When B1-01 = "0,"
Up/Down operation is disabled.
2. Upper limit speed = Maximum output speed (E1-06) × Speed Reference
Upper Limit (D2-01), if used.
3. The lower limit value is the larger of either the master Speed reference from
control circuit terminals 13 or 14, or the Speed Reference Lower Limit (D2-02).
4. With Hold Reference Memory Selection is enabled (D4-01 = "1") and a hold
command input, the output frequency stored even after the power supply
turns OFF. When D4-01 = "0" the output frequency is not stored.
5. If the jog frequency reference is input during Up/Down operation, the jog fre-
quency reference has priority.
• Forward and Reverse JOG commands (settings: Fwd Jog = "12," Rev Jog = "13")
Enables forward and reverse run jog frequency commands.
Setting
12
13
64
UP command
Closed
DOWN command
Open
Operation Status
Accel
D H U
H
D
H
Figure 33 UP/DOWN Command Timing Diagram
When closed-run forward at jog frequency reference (D1-09).
When closed-run reverse at jog frequency reference (D1-09).
Open
Open
Closed
Open
Decel
Hold
U
H
D
D1
H
U
Description
Closed
Closed
Hold
U1
H
D
D1
H
VS-616PS5 Programming Manual