YASKAWA VS-616PS5 Series Programming Manual page 79

Brushless motor drive
Hide thumbs Also See for VS-616PS5 Series:
Table of Contents

Advertisement

H4-03 Terminal 21 Analog Output Bias
Setting Range:
Factory Default:
Sets the terminal 21 output bias for the analog output monitors. To obtain the output
level, multiply the monitor output level by the gain value set in H4-02, then add the
bias value set in H4-03.
H4-04 Terminal 23 Analog Output Selection
Selects the analog output monitors for terminal 23 (see Terminal 21 Analog Output
Selection). The resolution of terminal 23 is 9 bits plus a sign bit.
Terminal 23 Analog Output
H4-05
Setting Range:
Factory Default:
Sets the terminal 23 output gain for the analog output monitors. To obtain the output
level, multiply the monitor output level by the gain value set in H4-05, (see Figure 48).
H4-06 Terminal 23 Analog Output Bias
Setting Range:
Factory Default:
Sets the terminal 23 output bias for the analog output monitors. To obtain the output
level, multiply the monitor output level by the gain value set in H4-05, then add the
bias value set in H4-06, (see Figure 48).
H4-07
Selects the type of voltage signal output at terminals 21 and 23.
VS-616PS5 Programming Manual
±109.2%
0.0%
+10
Bias (%)
0
-10
Figure 48 Analog Output Gain and Bias Adjustment
Gain
±300.0%
1.0
±109.2%
0.0%
Analog Output Signal Selection
Setting
0
1
Section H: Control Circuit Terminal Parameters
2.50
1.00
0
Reference (%)
Description
0 to 10V output (factory default)
±10V output
H4 Analog Outputs
Gain
B
B
B
B
B
79