H4: Analog Outputs - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

1.10 H: Terminal Functions
Setting Value
Function
25
PI2 Control Setpoint
26
PI2 Control Feedback
27
PI Auxiliary Control
Feedback
2B
Emergency Override PID
Feedback
2C
Emergency Override PID
Setpoint
2D
Differential Level Source
2E
HAND Frequency Ref or
Setpoint
30
DWEZ Analog Input 1
31
DWEZ Analog Input 2

H4: Analog Outputs

No.
Name
(Hex.)
H4-01
Terminal FM Analog
Output Select
(041D)
H4-02
Terminal FM Analog
Output Gain
(041E)
RUN
72
V/f
OLV/PM
OLV/PM EZOLV
Enters the PI2 Control setpoint level as a percentage of the S3-02 [PI2 Control Transducer Scale] value.
Note:
Parameters S3-03 [PI2 Control Decimal Place Pos] and S3-04 [PI2 Control Unit Selection] set the resolution and
unit.
V/f
OLV/PM
OLV/PM EZOLV
Enters the PI2 Control feedback level as a percentage of the S3-02 [PI2 Control Transducer Scale] value.
Note:
Parameters S3-03 [PI2 Control Decimal Place Pos] and S3-04 [PI2 Control Unit Selection] set the resolution and
unit.
V/f
OLV/PM EZOLV
OLV/PM
Enters the PI Auxiliary Control feedback value when YF-01 = 1 [PI Aux Control Selection = Enabled].
Note:
• The full-scale of the analog signal goes from 0% to YF-02 [PI Aux Control Transducer Scale].
• Parameter YF-22 [PI Aux Level Decimal Place Pos] sets the resolution.
V/f
OLV/PM
OLV/PM EZOLV
This input is the PID Feedback source when Emergency Override is running in PID mode (S6-02 = 2 or 3 [Emergency
Override Ref Selection = System PID Mode or Independent PID Mode]).
Note:
• When S6-02 = 2 [Emergency Override Ref Selection = System PID Mode], the full-scale of the analog signal
goes from b5-71 [Min PID Transducer Scaling] to b5-38 [PID User Unit Display Scaling].
• When S6-02 = 3 [Independent PID Mode], the full-scale of the analog signal goes from b5-71 to S6-03 [EMOVR
Independent PID Scale].
• When you set MEMOBUS register 3A93h bit 4, register 3A95h becomes the Emergency Override Feedback
source.
V/f
OLV/PM
OLV/PM EZOLV
This input is the PID Setpoint source when Emergency Override is running in PID mode (S6-02 = 2 or 3 [Emergency
Override Ref Selection = System PID Mode or Independent PID Mode]).
Note:
• When S6-02 = 2 [Emergency Override Ref Selection = System PID Mode], the full-scale of the analog signal
goes from b5-71 [Min PID Transducer Scaling] to b5-38 [PID User Unit Display Scaling].
• When S6-02 = 3 [Independent PID Mode], the full-scale of the analog signal goes from b5-71 to S6-03 [EMOVR
Independent PID Scale].
• When you set MEMOBUS register 3A93h bit 5, register 3A96h becomes the Emergency Override Setpoint
source.
V/f
OLV/PM EZOLV
OLV/PM
Enters a feedback value to calculate the Differential Level between the Differential Level Source feedback and the
primary PID Feedback [H3-xx = B].
Note:
The full-scale of the analog signal goes from b5-71 [Min PID Transducer Scaling] to b5-38 [PID User Unit
Display Scaling].
V/f
OLV/PM EZOLV
OLV/PM
Enters the S5-05 [HAND Frequency Reference] value or the S5-06 [HAND Setpoint] value. When S5-01 = 0 [HAND
Frequency Reference Source = HAND Analog Input] and S5-03 = 0 [HAND Mode PI Selection = Disabled], the drive
enters HAND Frequency Reference. When b5-01 ≠ 0, S5-01 = 0, and S5-03 = 1 [Enabled], the drive enters HAND
Setpoint.
Note:
• When PID is enabled, the full-scale of the analog signal goes from b5-71 [Min PID Transducer Scaling] to b5-38
[PID User Unit Display Scaling].
• When PID is disabled, the drive enters this analog signal as the percentage of the E1-04 [Maximum Output
Frequency] value.
V/f
OLV/PM
OLV/PM EZOLV
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV/PM EZOLV
OLV/PM
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV/PM
OLV/PM EZOLV
Sets the monitor number to send from MFAO terminal FM.
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-01 = 102 to monitor U1-02
[Output Frequency].
V/f
OLV/PM EZOLV
OLV/PM
Sets the gain of the monitor signal that is sent from MFAO terminal FM.
Sets the analog signal output level from the terminal FM at 10 V or 20 mA as 100% when
an output for monitoring items is 100%.
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Ref.
335
335
335
335
335
335
335
336
336
Default
Ref.
(Range)
102
337
(000 - 999)
100.0%
337
(-999.9 - +999.9%)