Section H: Control Circuit Terminal Parameters
H1 Digital Inputs
ing table to choose the desired response upon inputting an external fault command.
Input Level
Selection
N.O.
N.C.
÷
—
÷
—
÷
—
÷
—
÷
—
÷
—
÷
—
÷
—
—
÷
—
÷
—
÷
—
÷
—
÷
—
÷
—
÷
—
÷
Notes:
1. N.O. = normally open contact; N.C. = normally closed contact
2. Setting "24" is the factory default.
3. Set up the external fault function according to the following tree.
H1 XX = "24"
Depress
the
66
External Fault Selection
Detection Method
During
Ramp to
Always
Run
Stop
÷
—
÷
—
—
÷
—
—
÷
—
—
—
÷
—
÷
—
—
÷
—
—
÷
—
÷
—
÷
—
—
÷
—
—
÷
—
—
—
÷
—
÷
—
—
÷
—
—
÷
—
Depress the Data/Enter key.
Input Level Selection
Detection Method
∧
key.
External Fault Action
External Fault Action
Coast to
Fast-stop
Stop
÷
—
—
÷
—
—
÷
—
—
÷
—
—
÷
—
—
÷
—
—
÷
—
—
÷
—
—
÷
—
—
÷
—
—
÷
—
—
÷
—
—
N.O. Contact
N.C. Contact
Always
During Run
Ramp to Stop
Coast to Stop
Fast-stop
Alarm Only
Setting
Result
Alarm Only
—
20
—
24
—
28
÷
2C
—
22
—
26
—
2A
÷
2E
—
21
—
25
—
29
÷
2D
—
23
—
27
—
2B
÷
2F
VS-616PS5 Programming Manual