H4 Analog Outputs - YASKAWA F7 Programming Manual

Hide thumbs Also See for F7:
Table of Contents

Advertisement

An analog input filter can be used to prevent erratic Drive control when a "noisy" analog reference is used. Parameter H3-12
sets the time constant for a first order filter that will be applied to both the A1, A2, and A3 analog inputs. The Drive operation
becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing analog signals.
Noisy

H4 Analog Outputs

H4-01 Terminal FM Monitor Selection
Setting Range:
1 to 45
Factory Default: 2: Output Freq
The FM and AM analog output terminals can be programmed to output a 0 to 10 Vdc, -10 to +10 Vdc, or 4 to 20 mA signal
proportional to any one of functions detailed in the table below.
Parameter
Setting
1
Frequency Reference
2
Output Frequency
3
Output Current
5
Motor Speed
6
Output Voltage
7
DC Bus Voltage
8
Output kWatts
9
Torque Reference
15
Terminal A1 Input Level
16
Terminal A2 Input Level
17
Terminal A3 Input Level
18
Motor Secondary Current
19
Motor Excitation Current
20
SFS Output
21
ASR Input
22
ASR Output
24
PID Feedback
26
Output Voltage Reference Vq
27
Output Voltage Reference Vd
31
Not Used
32
ACR (q) Output
33
ACR (d) Output
input
signal
Fig. 76 Analog Input Filter Time Constant Effect on "Noisy" Signal
Table 21 Analog Output Functions
Function
Programming 105
Analog
Input
Filter
Internal Analog Input Value
V/f
O
O
O
X
O
O
O
X
O
O
O
O
X
O
X
X
O
X
X
O
X
X
Analog
(Filtered)
input post
Control Method (A1-02)
Open
V/f with
Loop
PG
Vector
O
O
O
O
O
O
O
O
O
O
O
O
O
O
X
O
O
O
O
O
O
O
O
O
X
O
O
O
O
X
O
X
O
O
X
O
X
O
O
O
X
O
X
O
Flux
Vector
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O