Section H: Control Circuit Terminal Parameters
H3 Analog Inputs
H3-06 Terminal 16 Reference % Gain
Setting Range:
Factory Default:
Sets the terminal 16 input gain level when the reference voltage is 10V, (see Figure
46).
H3-07 Terminal 16 Reference ±% Bias
Setting Range:
Factory Default:
Sets the terminal 16 input bias level when the reference voltage is 0V, (see Figure
46).
H3-08 Terminal 14 Signal Selection
Selects the type of signal input at terminal 14.
The resolution of terminal 14 is 11 bit, plus a sign bit. (10 bit for 4-20mA input).
Note:
H3-09 Terminal 14 Multi-function Selection
Selects the multi-function analog input function for terminal 14 (see Terminal 16 Multi-
function Selection for details).
H3-10 Terminal 14 Reference % Gain
Setting Range:
Factory Default:
Sets the terminal 14 input gain level when the reference current is 20mA, (see Figure
46).
76
0.0 to 1000.0%
100.0%
±100.0%
0.0%
Setting
0
0 to 10V input
1
-10V to +10V input
2
4 to 20mA (factory default)
To enable terminal 14 for a voltage signal (settings: "0" or "1"), cut
jumper wire J1 on the control printed circuit board. J1 is located on the
bottom left-hand corner of the control board directly behind terminal 13.
0.0 to 1000.0%
100.0%
Description
VS-616PS5 Programming Manual
A
A
A
A