H4: Analog Outputs - YASKAWA CIPR-CR70A Series Technical Manual

Ac drive for cranes 200/400 v class: 0.4 to 110/315 kw
Table of Contents

Advertisement

Setting
Function
11
Reverse Torque
Limit
12
Regenerative
Torque Limit
14
Torque
Compensation
15
General Torque
Limit
1F
Not Used

H4: Analog Outputs

No.
Name
(Hex.)
H4-01
Terminal FM Analog
Output Select
(041D)
H4-02
Terminal FM Analog
Output Gain
(041E)
RUN
H4-03
Terminal FM Analog
Output Bias
(041F)
RUN
H4-04
Terminal AM Analog
Output Select
(0420)
H4-05
Terminal AM Analog
Output Gain
(0421)
RUN
H4-06
Terminal AM Analog
Output Bias
(0422)
RUN
H4-07
Terminal FM Signal
Level Select
(0423)
H4-08
Terminal AM Signal
Level Select
(0424)
H4-20
Analog Power
Monitor 100% Level Sets the level at 10 V when U1-08 [Output Power] executes analog output.
(0B53)
YASKAWA ELECTRIC SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Enters the load torque limit if the motor rated torque is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Enters the regenerative torque limit if the motor rated torque is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Inputs the torque compensation value assuming that the motor rated torque is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Enters the torque limit that is the same for all quadrants for forward, reverse, and
regenerative operation if the motor rated torque is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Value for terminals that are not being used or terminals being used in through mode.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor number to send from MFAO terminal FM.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the Ux-xx monitor signal in H4-01 [Terminal FM Analog
Output Select].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the Ux-xx monitor signal in H4-01 [Terminal FM Analog
Output Select].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitoring number to be output from the MFAO terminal AM.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the Ux-xx monitor signal in H4-04 [Terminal AM Analog
Output Select].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the Ux-xx monitor signal in H4-04 [Terminal AM Analog
Output Select].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MFAO terminal FM output signal level.
0 : 0 to 10 Vdc
1 : -10 to +10 Vdc
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MFAO terminal AM output signal level.
0 : 0 to 10 Vdc
1 : -10 to +10 Vdc
V/f
CL-V/f
OLV
CLV
AOLV
Description
10 Parameter List
Ref.
692
692
692
692
692
Default
(Range)
102
(000 - 999)
100.0%
(-999.9 - +999.9%)
0.0%
(-999.9 - +999.9%)
103
(000 - 999)
50.0%
(-999.9 - +999.9%)
0.0%
(-999.9 - +999.9%)
0
(0, 1)
0
(0, 1)
0.00 kW
(0.00 - 650.00 kW)
471