H4: Analog Outputs - YASKAWA iQpump1000 Quick Start Manual

Ac drive
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

B.7 H Parameters: Multi-Function Terminals
H3-oo
Function
Setting
Water Level or Suction
23
Input
25
Secondary PI Setpoint
26
Secondary PI Feedback PI2 Feedback
<1> When Pressure Control is enabled (Q5-01 = 1), the action of the analog input is normal. A higher voltage or current on the input causes a higher
pressure to be read in the drive.
<2> When Vacuum Control is enabled (Q5-01 = 2), the action of the analog input is reversed. A higher voltage or current on the input causes a lower
pressure (or higher level of vacuum) to be read in the drive.
u

H4: Analog Outputs

No.
(Addr.
Name
Hex)
Multi-Function Analog
H4-01
Output Terminal FM
(041D)
Monitor Selection
H4-02
Multi-Function Analog
(041E)
Output Terminal FM
Gain
H4-03
Multi-Function Analog
(041F)
Output Terminal FM
Bias
Multi-Function Analog
H4-04
Output Terminal AM
(0420)
Monitor Selection
H4-05
Multi-Function Analog
(0421)
Output Terminal AM
Gain
H4-06
Multi-Function Analog
(0422)
Output Terminal AM
Bias
Multi-Function Analog
H4-07
Output Terminal FM
(0423)
Signal Level Selection
Multi-Function Analog
H4-08
Output Terminal AM
(0424)
Signal Level Selection
286
H3 Multi-Function Analog Input Settings
LCD Display
When Water Level Control is enabled (Q4-01 = 1):
0 V or 4 mA = 0 (ft)
10 V or 20 mA = Q4-02 (PSI) * 2.308 ft/PSI OR
When Suction Pressure Control is enabled (Q5-01 = 1)
WaterLvl/Suction
0 V or 4 mA = 9 (PSI)
10 V or 20 mA = Q5-02 (PSI) OR
When Vacuum Control is enabled (Q5-01 = 2)
0 V or 4 mA = 0 ("Hg)
10 V or 20 mA = Q5-02 ("Hg)
PI2 Setpoint
10 V = S3-02 (maximum output frequency)
10 V = S3-02 (maximum output frequency)
LCD Display
Selects the data to be output through multi-function analog
output terminal FM.
Term FM FuncSel
Set the desired monitor parameter to the digits available in
Uo-oo.
For example, enter "103" for U1-03.
Sets the signal level at terminal FM that is equal to 100% of the
selected monitor value.
Terminal FM Gain
Sets the signal level at terminal FM that is equal to 0% of the
selected monitor value.
Terminal FM Bias
Selects the data to be output through multi-function analog
output terminal AM.
Terminal AM Sel
Set the desired monitor parameter to the digits available in
Uo-oo.
For example, enter "103" for U1-03.
Sets the signal level at terminal AM that is equal to 100% of the
selected monitor value.
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 0% of the
selected monitor value.
Terminal AM Bias
Level Select1
0: 0 to 10 V
0: 0-10 VDC
1: -10 to 10 V
1: -10 +10 VDC
2: 4 to 20mA
2: 4-20 mA
AO Level Select2
0: 0 to 10 V
0: 0-10 VDC
1: -10 to 10 V
1: -10 +10 VDC
2: 4 to 20 mA
2: 4-20 mA
Description
Description
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
<1>
<2>
Values
Default: 102
Range: 000 to
999
Default: 100.0%
Min.: -999.9
Max.: 999.9
Default: 0.0%
Min.: -999.9
Max.: 999.9
Default: 103
Range: 000 to
999
Default: 50.0%
Min.: -999.9
Max.: 999.9
Default: 0.0%
Min.: -999.9
Max.: 999.9
Default: 0
Range: 0 to 2
Default: 0
Range: 0 to 2
Page
Page
162
163
163
162
163
163
164
164