O2-08 Cumulative Operation Time Selection
Defines the operation time that accumulates in the timer.
Setting
0
Power-On time is the accumulated time (factory default).
The timer counts the time while the inverter power supply is turned ON as operation time.
1
Running time is the accumulated time. The timer counts the time while the inverter is running as
operation time.
After changing this setting, reinitialize the inverter in parameter A1-03. This initializa-
tion affects application dependent parameter settings (motor-related parameters, car-
rier frequency, inverter rated current, etc.).
VS-616PS5 Programming Manual
Section O: Operator Parameters
Description
O2 Key Selection
A
99