Section B: Application Parameters
B1 Sequence
Coast to Stop with Timer 1 (B1-03 = "3")
Output Frequency
FWD (REV)
Run Command
Upon removal of the run command, a new run command is blocked until the coast to
stop timer has elapsed (same as Decel 1). After the timer elapses, the user must
enter another run command for the inverter to begin acceleration. This stopping
method is disabled during flux vector control.
B1-04 Reverse Operation Enable/Disable
Setting Range:
Factory Default:
A "reverse run disabled" setting does not allow a reverse run command from the con-
trol circuit terminal or the digital operator. This setting is used in applications where a
reverse run command is undesirable.
Setting
B1-05 Operation Selection at Zero Speed
Select an operation mode to be used when the speed reference (analog input) drops
below the minimum speed setting (El -08).
Setting
0
12
Coasting
ON
Run Command Disabled
Figure 4 Stopping Method - Coast to Stop w/Timer
0 to 1
0
0
Reverse run is enabled (factory default).
1
E1-08 is ignored, run according to speed reference.
Decel Time 1
(C1-02)
ON
ON
Description
Reverse run is disabled.
Description
VS-616PS5 Programming Manual
Accel Time 1
(C1-01)
Time
B
A