Mitsubishi QCPU Structured Programming Manual page 157

Melsec-q series
Hide thumbs Also See for QCPU:
Table of Contents

Advertisement

Control Data
Device
Item
Error completion type
[0]
S1
Completion status
[1]
S1
Channel used by host
[2]
S1
station
Target station's CPU type
[3]
S1
Target station network No.
[4]
S1
Target station No.
[5]
S1
5.4 CC-Link IE Controller Network, MELSECNET/H, and Ethernet Instruction
Setting data
b15
to
0
Error completion type (bit 7)
Specify the clock data setup status at the time of error completion.
0: Clock data at the time of error completion is not set in the area starting
from [11].
1: Clock data at the time of error completion is set in the area starting
from
[11].
S1
S1
The instruction completion status is stored.
0
: Normal completion
Other than 0
: Error completion (error code)
Specify the channel used by the host station.
1 to 8: Channel
Specify the type of the target station CPU.
Setting value
Target station CPU/host system CPU
0000
H
(Specified data are the same as '03FF
*1
Target station CPU/host system CPU
03FF
H
Target station CPU/host system CPU
0000
H
(Specified data are the same as '03FF
Multi-CPU No. 1/target station CPU (single
*2
03E0
H
CPU system)
*2
Multi-CPU No. 2
03E1
H
*2
Multi-CPU No. 3
03E2
H
*2
Multi-CPU No. 4
03E3
H
*1
Target station CPU/host system CPU
03FF
H
Specify the network number of the target station.
1 to 239
: Network number
254
: Specify this when 254 has been set in Jn.
(
Network specified in 'Valid module during other station
access')
Specify the station number of the target station.
(1) Station number specification
Ethernet
MELSECNET/H
CC-Link IE
Universal model QCPU
controller network
High Performance model QCPU 1 to 64
(2) Group specification
81
to A0
: All stations in group numbers 1 to 32 (Available only at clock
H
H
data writing and remote RUN/STOP)
Group No.1・・・81
Group No.2・・・82
Group No.32・・・A0
(3) All stations specification
FF
: All stations of the target network number (Except the host
H
station.) (Available only at clock data writing and remote RUN/
STOP)
To specify a group or all stations, set '0000
station's CPU type (
[3]).
S1
b7
to
b4
to
b0
0
1
0
1
Description
'.)
H
'.)
H
1 to 64
1 to 120
H
H
to
H
' or '03FF
' for Target
H
H
5.4.8 REQ instruction
J_REQ, G_REQ
*1
Setting range
Setting side
0011
,
H
User
0091
H
System
1 to 8
User
0000
,
H
03FF
H
User
0000
,
H
03E0
to
H
03E3
,
H
03FF
H
1 to 239, 254
User
1 to 120,
81
to A0
,
User
H
H
FF
H
5-119
5

Advertisement

Table of Contents
loading

Table of Contents