Mitsubishi QCPU Structured Programming Manual page 143

Melsec-q series
Hide thumbs Also See for QCPU:
Table of Contents

Advertisement

Device
Item
Target station No.
[5]
S1
[6]
S1
Number of resends
[7]
S1
Arrival monitoring time
[8]
S1
5.4 CC-Link IE Controller Network, MELSECNET/H, and Ethernet Instruction
Setting data
Specify the station number of the target station.
(1) Station number specification
Ethernet
MELSECNET/H
Universal model QCPU
CC-Link IE
controller network
High Performance model QCPU 1 to 64
To increase the data reliability when the station number is specified,
executing the instruction with setting Execution/Error completion type
(
[0]) to '1: With arrival confirmation' is recommended.
S1
(2) Group specification
81
to A0
: All stations in group numbers 1 to 32
H
H
(Setting is available when Execution type is set to '0: Without
arrival confirmation' in
[0].)
S1
Group No.1・・・81
Group No.2・・・82
Group No.32・・・A0
(3) All stations specification
FF
: All stations of the target network number (Except the host
H
station.)
(Setting is available when Execution type is set to '0: Without
arrival confirmation' in
[0].)
S1
To specify a group or all stations, set '0000
station's CPU type (
[3]).
S1
(Fixed value)
For instruction execution
Specify the number of resends when the instruction is not completed
within the monitoring time specified in
Execution type is set to '1: With arrival confirmation' in
At instruction completion
The number of resends (result) is stored. (Setting is available when
Execution type is set to '1: With arrival confirmation' in
Specify the monitoring time required for instruction completion. (Setting
is available when Execution type is set to '1: With arrival confirmation' in
[0].)
S1
If the instruction is not completed within this time, it is resent by the
number of times specified in
[7].
S1
Description
0 to TCP retransmission
timer value: Monitoring is
performed by the TCP
retransmission timer value.
Ethernet
(TCP retransmission timer
value + 1) to 16383:
Monitoring time (unit:
second)
MELSECNET/H
0: 10 seconds
CC-Link IE
1 to 32767: 1 to 32767
controller network
seconds
1 to 64
1 to 120
H
H
to
H
' or '03FF
' for Target
H
H
[8]. (Setting is available when
S1
[0].)
S1
[0].)
S1
Setting value
0 to 16383
0 to 32767
5.4.3 WRITE instruction
J_WRITE, G_WRITE
*1
Setting range
Setting side
1 to 120,
81
to A0
User
H
H,
FF
H
0
User
0 to 15
User
System
0 to 32767
User
5-105
5

Advertisement

Table of Contents
loading