Cc-Link Instruction; Rird Instruction - Mitsubishi QCPU Structured Programming Manual

Melsec-q series
Hide thumbs Also See for QCPU:
Table of Contents

Advertisement

G_RIRD
5.3

CC-Link Instruction

5.3.1

RIRD instruction

GP_RIRD
Structured ladder
G_RIRD
EN
ENO
Un*
d1
s
d2
Input argument
EN:
Un*:
s:
Output argument
ENO:
d1:
d2:
Function
This instruction reads data for the specified number of points from the buffer memory of the CC-
Link module or the device of the programmable controller CPU module on the specified station.

5.3 CC-Link Instruction

5-80
5.3.1 RIRD instruction
ST
ENO:=
(EN, Un*, s, d1, d2);
G_RIRD
Executing condition
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/O number in
three digits)
Variable that stores control data
Execution result
Start number of the device that stores read data
Variable that turns ON upon completion of the instruction
d2[1] also turns ON at the time of error completion.
Internal device
Setting
R, ZR
*1
data
Bit
Word
S
d1
d2
P: Executing condition
instructions.
G_RIRD
GP_RIRD
:Bit
:ANY16
:Array of ANY16 [0..4]
:Bit
:ANY16
:Array of bit [0..1]
J
\
U
Bit
Word
*1: Local devices and file registers per program cannot be used as setting data.
G_RIRD
:
indicates any of the following
Zn
Constant Others
\G

Advertisement

Table of Contents
loading

Table of Contents