Mitsubishi QCPU Structured Programming Manual page 141

Melsec-q series
Hide thumbs Also See for QCPU:
Table of Contents

Advertisement

Control Data
Device
Item
Execution/Error completion
[0]
S1
type
5.4 CC-Link IE Controller Network, MELSECNET/H, and Ethernet Instruction
Setting data
b15
to
b7
0
Execution type (bit 0)
0: Without arrival confirmation
When the target station is on the same network... Completed when
Completed
Execution source
Target station
When the target station is on another network ..... Completed when
Completed
Relay station
Execution source
1: With arrival confirmation
Completed when data are written to the target station.
Completed
Target station
Execution source
0: Without arrival confirmation
• When the target station is on the same network
Completed when data are sent from the host station.
Request source
Completed
• When the target station is on another network
Completed when data reach to a relay station on the same
network.
Request source
Relay station
Completed
1: With arrival confirmation
Completed when data are written to the target station.
Relay station
Request source
Completed
Target station
When '0: Without arrival confirmation' is specified, even if writing to
the target station is completed abnormally in the following cases,
the processing of the instruction in the host station is completed
normally.
• Communication itself was completed normally, although the
sent data were erroneous.
• Data could not be written to the target station because
instructions from multiple stations were executed to the same
station. (An error code (E006
H
target station.)
to
b0
0
data are sent
from the host
station.
data reach to a
relay station on
the same
network.
Target station
Relay station
Target station
Completed
Target station
Target station
Completed
Target station
or E205
) is detected at the
H
5.4.3 WRITE instruction
J_WRITE, G_WRITE
*1
Setting range
Setting side
0000
,
H
0001
,
H
User
0080
,
H
0081
H