Mitsubishi QCPU Structured Programming Manual page 149

Melsec-q series
Hide thumbs Also See for QCPU:
Table of Contents

Advertisement

Device
Item
Execution/Error completion
[0]
S1
type
Completion status
[1]
S1
Channel used by host
[2]
S1
station
Target station channel
[3]
S1
Target station network No.
[4]
S1
Target station No.
[5]
S1
[6]
S1
Number of resends
[7]
S1
5.4 CC-Link IE Controller Network, MELSECNET/H, and Ethernet Instruction
Setting data
Error completion type (bit 7)
Specify the clock data setup status at the time of error completion.
0: Clock data at the time of error completion is not set in the area
starting from
[11].
S1
1: Clock data at the time of error completion is set in the area starting
from
[11].
S1
The instruction completion status is stored.
0
: Normal completion
Other than 0
: Error completion (error code)
Specify the channel used by the host station.
1 to 8: Channel
Specify the channel of the target station that stores data.
1 to 8: Channel
Specify the network number of the target station.
1 to 239
: Network number
254
: Specify this when 254 has been set in Jn.
(Network specified in 'Valid module during other
station access')
Specify the station number of the target station.
(1) Station number specification
Ethernet
MELSECNET/H
Universal model QCPU
CC-Link IE
controller network
High Performance model QCPU 1 to 64
To increase the data reliability when the station number is specified,
executing the instruction with setting Execution/Error completion type
(
[0]) to '1: With arrival confirmation' is recommended.
S1
(2) Group specification
81
to A0
: All stations in group numbers 1 to 32
H
H
(Setting is available when Execution type is set to '0: Without
arrival confirmation' in
[0].)
S1
Group No.1・・・81
Group No.2・・・82
Group No.32・・・A0
(3) All stations specification
FF
: All stations of the target network number (Except the host
H
station.)
(Setting is available when Execution type is set to '0: Without
arrival confirmation' in
[0].)
S1
To specify a group or all stations, set '0000
station's CPU type (
[3]).
S1
(Fixed value)
For instruction execution
Specify the number of resends when the instruction is not completed
within the monitoring time specified in
Execution type is set to '1: With arrival confirmation' in
At instruction completion
The number of resends (result) is stored. (Setting is available when the
Execution type is set to '1: With arrival confirmation' in
1 to 64
1 to 120
H
H
to
H
' or '03FF
' for Target
H
H
[8]. (Setting is available when
S1
[0].)
S1
[0].)
S1
5.4.5 SEND instruction
J_SEND, G_SEND
*1
Setting range
Setting side
0000
,
H
0001
,
H
User
0080
,
H
0081
H
System
1 to 8
User
1 to 8
User
1 to 239, 254
User
1 to 120,
81
to A0
,
User
H
H
FF
H
0
User
0 to 15
User
System
5-111
5

Advertisement

Table of Contents