CHAPTER 6

Clearance Requirements

Clearance Requirements for Airflow and Hardware Maintenance on ACX2200 Routers
Copyright © 2017, Juniper Networks, Inc.

Clearance Requirements for Airflow and Hardware Maintenance on ACX2200

Routers on page 33
When planning the installation site, allow sufficient clearance around the rack (see
Figure 11 on page
33):
For service personnel to remove and install hardware components, allow at least
2.16 in. (5.5 cm) in front of the router.
The rack or cabinet must have an adequate supply of cooling air.
Ensure that the cabinet allows the chassis hot exhaust air to exit from the cabinet
without recirculating into the router.
When deploying the router in harsh environments where the router may operate
between 131° F (55° C) and 149° F (65° C), allow a 1-rack unit (U) gap above and
below the router.
Ensure that there is a minimum of 1 meter/second airflow in any direction.

Figure 11: ACX2200 Chassis Dimensions and Clearance Requirements

2.16" (5.5 cm)
clearance required
3" (7.6 cm)
for the cables
(24 cm)
19.2"
Front
(48.7 cm)
3" (7.6 cm)
Front-mounting flange
.75" (2 cm)
clearance required
for free airflow
9.4"
17.5"
Rear
(44.5 cm)