Acx2200 Dc Power Specifications; Power Specifications; Table 22: Dc Power Electrical Specifications - Juniper ACX2200 Hardware Manual

Universal access router
Hide thumbs Also See for ACX2200:
Table of Contents

Advertisement

ACX2200 DC Power Specifications

Copyright © 2017, Juniper Networks, Inc.
NOTE:
In North America, AC power cords must not exceed approximately
14.75 ft (4.5 m) in length, to comply with National Electrical Code (NEC)
Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical Code
(CEC) Section 4-010(3). You can order AC power cords that are in compliance.
CAUTION:
Power cords and cables must not block access to device
components or drape where people could trip on them.
The power supply in ACX2200 routers is built in along the front left panel of the chassis
with DC power terminals to connect power to the router.
When the ACX2200 router are operating normally and both power supplies are switched
on, load sharing between them occurs automatically. When one power supply fails or is
turned off, the other power supply immediately assumes the entire electrical load for
the system. A single power supply can provide full power for as long as the router is
operational.
NOTE:
When only one power supply is available on an ACX2200 router, we
recommend that you connect both the power inputs to the same source.
That is, connect both the DC power inputs of the ACX2200 router to the only
available power supply. Doing so ensures that you get the maximum amount
of hold-up time during a power failure.
ACX2200 routers support a wide range of voltage ranges as shown in

Table 22: DC Power Electrical Specifications

Item
DC input voltages
DC input currents
Power supply output
Chapter 10: Power Specifications
Specification
20 to 30 VDC
–39 to –56 VDC
–39 to –72 VDC
10 A @ 24 VDC
5 A @ –48 VDC
4 A @ –60 VDC
200 W
Table 22 on page
45.