104 en | Area Wide Parameters
This parameter determines if opening and closing activity is reported when it occurs inside an
opening or closing window as programmed in O/C Windows.
Reports are always logged and printed on a local printer, if installed.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Disable O/C in Window
4.1.25

Auto Close

Default: No
Selections:
With this parameter, the control panel can automatically arm the area All On Delay at the end
of the closing window regardless of the previous armed state.
Regardless of Force Arm/Bypass Max, page 93 or Bypassable, page 196, an unconditional force
arm occurs resulting in faulted points being left out of the system. Refer to Force Arm
Returnable, page 196 or Bypass Returnable, page 196 for details on returning these points to
service.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Auto Close
4.1.26

Fail to Open

Default: No
Selections:
This parameter allows you to determine if a Fail to Open report is sent for this area. This
parameter can also be used to determine if a user failed to disarm the area before the opening
window expired.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Fail To Open
4.1.27

Fail to Close

Default: No
Selections:
2017.03 | 09 | F.01U.303.998
Yes - do not send opening and closing reports to the central station if they occur inside an
active window. If an opening or closing report occurs outside of a window, send it with
an early or late modifier. Refer to O/C Windows.
The active window must be a closing window for closing reports. It must be an
opening window for opening reports.
No - send opening and closing reports to the central station even when they occur inside
a programmed window. If an opening or closing occurs outside of the appropriate
window, it reports but does not have an early or late modifier.
 If you want to monitor all opening and closing activity, but you also want to use
features provided by opening and closing windows, set this parameter to No, and
program appropriate O/C windows.
Yes - the area automatically arms All On Delay at the end of the close window. When the
area automatically arms, the control panel sends a closing report if area and/or account
reports are programmed to do so.
No - do not automatically arm the area at the end of the close window.
Yes - a Fail to Open report is sent for this area if the area is not disarmed when the
opening window stop time occurs.
No - a Fail to Open report is not sent for this area.
Yes - a Fail to Close report is sent for this area if the area is not armed when the closing
window stop time occurs.