en | Panel Wide Parameters
RPS Menu Location
Panel Wide Parameters > Miscellaneous > Fire Trouble Resound
3.15.10

Fire Drill Duration

Default: 20 min
Selections: 5 to 30 (minutes) (1-minute increments)
Use this parameter to set the duration (in minutes) of a fire drill initiated from a fire keypad.
RPS Menu Location
Panel Wide Parameters > Miscellaneous > Fire Drill Duration
3.15.11

Early Ambush Time

Default: 10
Selections: 5 to 30  (minutes) (1-minute increments)
Use this parameter to enter the amount of time allowed for the user to enter a second
passcode at the keypad when the Area parameter, Early Ambush?, page 99 is set to Yes.
If a second passcode is not entered before the Early Ambush Time ends, a Duress event is
generated based on the first user passcode.
RPS Menu Location
Panel Wide Parameters > Miscellaneous > Early Ambush Time
3.15.12

Second Ambush Code

Default: Unique
Selections:
This parameter determines whether the same passcode can be used to start and end the Early
Ambush?, page 99 process.
RPS Menu Location
Panel Wide Parameters > Miscellaneous > Second Ambush Code
3.15.13

Abort Window

Default: 30 sec
Selections: 15 to 45 (seconds) (1-sec increments)
Use this parameter to enter the number of seconds the control panel delays sending an alarm
event to the central station from a point assigned to a Point Index with the Alarm Abort, page
199 feature enabled.
Notice!
To meet UL requirements, the combined Entry Delay, page 190 and Abort Window time must
not exceed 60 sec.
Notice!
For SIA CP-01 Compliance, Abort Window is a required parameter.
If an alarm silence operation is performed before this time elapses, the alarm transmission is
aborted and the keypad shows an optional  message (Refer to Abort Display, page 117).
2017.03 | 09 | F.01U.303.998
Unique - the passcode used to end the Early Ambush Time, page 78 must be different
from the passcode used to disarm the area.
Any - the Early Ambush Time can be stopped using a different passcode, or the same
passcode used to disarm the area.
Program Entry Guide
Control Panel
Bosch Security Systems, Inc.