132 en | Output Parameters
8

Output Parameters

Outputs provide dry contact (normally open/closed) outputs for LED annunciation and other
applications as well as wet (12vdc on/off) voltage outputs for basic alarm system functions
(such as Bell output, Reset Sensors, etc.). The applications are endless, but primarily, outputs
are used to enhance a systems capability to perform output functions.
Output Types
Output Follows Point
Outputs can also be used to activate when a point programmed for, Output Response Type (in
the point index section), is off normal or in alarm event.
Output Reports
When output activity is reported to the receiver (Refer to Routing ), on-board outputs are
reported as follows: A(1) = 253, B(2) = 254, C(3) = 255, and others report as 001 to 58. The
output report is Relay Set Output #rrrr when the output is turned ON and Relay Set Output
#rrrr when the output is turned off. Output reports are also stored in the control panel
memory log.
Controlling Outputs
As mentioned, outputs can be activated depending upon events that exist with the control
panel. In addition, outputs can be controlled by the user using the [CHG OUTPUT?] function,
Output On/Output Off skeds, and the RPS.
The following programming tips, notes and applications are important for you to review prior
to programming your outputs.
Notice!
Do not attempt to use the CHG OUTPUTS? function to toggle outputs reserved for special
functions. Special function outputs are Area and control panel Wide output functions as well
as outputs assigned to KP# Entr Key Rly and Output Response Type.
Output C is always powered ON. Assigning any other output deactivates Output C so this
output can be used for other functions. When Output C is programmed for Reset Sensors,
power is always supplied from the AUX terminal of the control panel and the Output C
provides a path to common. Output C turns off the common connection during sensor reset.
2017.03 | 09 | F.01U.303.998
Panel Wide Outputs: These outputs are used to provide an output related to a "panel
wide" indication. For annunciation, these outputs can be used to indicate "system wide"
troubles for power, phone and overall control panel summary of alarms, troubles and
supervisory events.
Area Outputs: These outputs are used to provide an output "by the area" that the output
is assigned to. An area can have its own bell and sensor reset indications. Outputs can
also be used to indicate the area armed state and whether any off normal events such as
a force arm have occurred.
On-board Outputs: There are 2 on-board 12 VDC voltage-outputs which provide power
when activated on the control panel. These outputs are default programmed from the
factory as outputs A(1), B(2) and C(3). Typically, output A(1) is used for the Bell, output
B(2) is used for an alternate alarm output (such as another bell) and output C(3) is used
for Sensor Reset.
Off-board Outputs: The B9512G control panel can also control as many as 472 dry
contact form "C" outputs when up to 59 optional B308 OctoOutput Modules are installed.
The B8512G control panel supports up to 72 dry contact form "C" outputs when 9
optional B308 OctoOutput Modules are installed. These outputs are used for Area
Output, Panel Wide Output, and Individual Point Fault Outputs.