Ulc Compliance; Can/Ulc-S304 Compliance; Can/Ulc-S559, Required Programming - Bosch B9512G Program Entry Manual

Security system
Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panel
For each of the SIA CP-01-compliant parameters, ensure that the Minimum View and Edit
Security Levels match the minimum settings for this parameter. For example, if this
parameter's minimum view and edit security levels are 5, each compliant parameter must have
its levels set to 5.
RPS Menu Location
Compliance Verification > SIA CP-01 Verification
2.2

ULC Compliance

Default: No
Selections:
This parameter causes the control panel to disregard input from all sensors for a minimum of
120 seconds at system start-up.
When sensor processing is started, the control panel reports a unique event prior to reporting
any point events. Additionally, no power-induced events are reported unless it is determined
that the fault will not be restored within the 120 second delay time.
Notice!
Do not set both ULC Compliance and UL864 Fire Application to Yes
You can set one to Yes and one to No, or both to No.
RPS Menu Location
Compliance Settings > ULC Compliance
2.2.1

CAN/ULC-S304 compliance

CAN/ULC-S304, SIGNAL RECEIVING CENTRE AND PREMISE BURGLAR ALARM CONTROL
UNITS
This Standard covers construction and performance requirements for control units and
accessories for intrusion alarm systems, including protected premises control units and
accessories for local or signal receiving centre connections, and signal receiving centre alarm
receiving equipment, including recording equipment. The equipment is intended for use in
premises, safes and vaults.
Control panel programming requirements
Setting the ULC Compliance parameter to Yes is the one control panel programming
requirement for compliance with the CAN/ULC-S304 standard.
2.2.2

CAN/ULC-S559, Required Programming

CAN/ULC-S559, Standard for Equipment for Fire Signal Receiving Centres and Systems
CAN/ULC-S559 covers requirements for fire signal receiving centres and systems, which
include transmitting and receiving equipment, proprietary fire receiving centre equipment and
control unit accessories. Fire signal receiving centre systems include protected premise unit
and receiver for ordinary (non-hazardous) indoor and outdoor locations. Programming
methods, test, service and other software intended for use with the equipment for fire signal
receiving centres and systems are included in the evaluation of the equipment. Signal
receiving units used in fire signal receiving centres, satellite centres, signal processing centres
and bridging centres are also covered by the requirements in this Standard.
COMPLIANCE SETTINGS > UL Canada Compliance
Set the COMPLIANCE SETTINGS > UL Canada Compliance parameter to Yes.
Bosch Security Systems, Inc.
Yes. Adjust control panel operation for UL Canada (ULC) compliance.
No. Do not adjust for ULC compliance.
Program Entry Guide
Compliance Settings | en
2017.03 | 09 | F.01U.303.998
19