176 en | Points
10

Points

10.1

Point Assignments

10.1.1

Source

Default:
Selections:
Use this parameter to assign a point to a physical device.
Point Source indicates where specific point devices are allowed to be configured, and what
point ranges are allowed. When a selection is grayed out, you cannot use that option to
configure the point.
For the B9512G control panel, the Wireless selection is only available for points 9 to 512.
When the Point Source is set to Wireless, Output, or IP Camera, Debounce does not apply.
RPS automatically selects a dash (-) for Debounce, which indicates that Debounce is not
applicable.
Notice!
Point Source for points 1-8 is fixed as On-board and cannot be changed. To expand or
collapse the list of Point numbers, use the arrows at the top of the RPS screen.
RPS Menu Location
Points > Point Assignments > Source
10.1.2

Text

Default:  Point #
Selections: Up to 32 characters.
This parameter sets what is displayed at keypads and what is reported to the central station
receiver when transmitting in Modem4 format (if it is a reporting point).
Enter up to 32 characters of text, numbers and symbols to describe the point.
Keypads display the first 20 characters. If more than 20 characters are used, the text scrolls
across the display one time. To scroll the text again, press [ESC].
Spaces before, after and within a string of text are treated as text and are included in the 32
character limit.
2017.03 | 09 | F.01U.303.998
Points 1-8  On-board
All Other Points  Unassigned
Unassigned - point is not in use.
ZONEX - point is installed using the B600 retrofit module on ZONEX, or through the
D8125 Addressable Expansion Module.
Octo-input - point is installed on an SDI2 bus input module.
Keypad - point is installed on a keypad.
Wireless - point is installed on an SDI2 bus RF receiver.
On-board - point is installed on the control panel.
Output - logical connection to the output of the same number. Not installed on a physical
device.
IP Camera - point is installed on an IP Camera.
POPEX - point is installed on a B299 POPEX module.
Door - point is installed on a door module.