7.9.4

Auto Program

Shortcut:
0-PROG > 9-PROGRAM MUX >4- MUX BUS TYPE
By scanning the buses for missing or new multiplex
devices, this option allows the installer to configure the
DS7400M to operate with the existing devices on the
multiplex buses. The following display appears:
AUTO PROGRAM?
_____:YES(1)/NO(0)
Press [1] to continue auto programming or [0] to cancel.
When you press [1], the D7024 checks for pre-existing
programming errors where devices are incorrectly
programmed in the space required for a lower
addressed multi-point device, such as a dual point
module. If a point is programmed under another device,
the following error message appears for 5 sec, and the
auto programming process aborts:
ADDRESS ERROR 1
AT ADDRESS xxx
If no errors are found, the D7024 begins a scanning
process that takes approximately 1 min to complete,
while showing the following:
AUTO PROGRAM
RESTORING
PLEASE WAIT ...
When scanning is complete, the D7024 checks for
missing devices. Missing devices are addresses with no
devices on the multiplex buses, but programmed into
the D7024's site specific memory area. If missing
devices are detected, the D7024 shows the following
menu. ("xxx" is the missing device's first point address):
MISSING PT @ xxx
0- DELETE POINT
1- KEEP POINT
2- DEL REMAIN
3- KEEP REMAIN
Bosch | 7/05 | 31499J
D7024 | Operation and Installation Guide | 7.0 Control Panel Programming
Table 30:
Option
DELETE
POINT
KEEP
POINT
DEL
REMAIN
KEEP
REMAIN
When Point Delete is complete, the D7024 shows the
total number of points deleted from the control panel
for period of 5 sec. "sax" indicates the number of points
that were removed from the control panel's site-specific
configuration.
Missing Point Options
When selected
The missing point and any addresses it
implemented (up to eight for an octal input
module) are permanently deleted from the
site specific memory area. If the deleted
device is an I/O module, the output zones
programmed for the relay reset to 0. If addi-
tional devices are found to be missing, the
above display repeats for each missing
device.
The D7024 retains the programming for
the current point and continues scanning
for additional missing points.
The D7024 prompts with # KEY TO
CONFIRM. If [#/CMND] is pressed, all
missing points are deleted from the site-
specific memory area and the Auto Pro-
gram process continues with the Devices
Found Menu. If another key is pressed, the
current point remains and the control panel
continues scanning for additional missing
devices.
No additional points are deleted and the
Auto Program process continues with the
Device Found Menu. Points individually
deleted with the Delete Point command
before selecting the Keep Remain com-
mand remain deleted when Keep Remain is
selected.
Use the Delete Remaining feature with cau-
tion. Devices missing from the multiplex
buses during the Delete Remaining operation,
even momentarily, are permanently deleted.
These points do not operate and do not gen-
erate trouble conditions even if they are
returned to the bus.
AUTO PROGRAM
xxx POINTS DELETED
57