Dtmf Dialing; Phone Supervision Time; Alarm On Fail - Bosch B9512G Program Entry Manual

Security system
Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

Control Panel
RPS Menu Location
Panel Wide Parameters > Phone and Phone Parameters > Phone Destination (1 to 4) Format
3.1.3

DTMF Dialing

Default: Yes
Selections:
Before setting this parameter to No, verify the PSTN (Public Switch Telephone Network) the
control panel is connected to supports pulse dialing.
RPS Menu Location:
Panel Wide Parameters > Phone and Phone Parameters > DTMF Dialing
3.1.4

Phone Supervision Time

Default: 0
Selections:
The control panel tests the phone line approximately nine times a minute. If it detects a fault
on the phone line that lasts the number of seconds set at this parameter, it creates a phone
line fail event.
Keypads display phone line fail event and initiate a trouble tone if the Buzz on Fail, page 30
and Trouble Tone, page 115 parameters are set to Yes. If the Alarm on Fail, page 29 parameter
is set to Yes, keypads display an alarm event and sound the alarm tone.
When the control panel detects a normal phone line (fault is cleared) for the number of
seconds set at this parameter, it creates a phone line restoral event.
The control panel sends phone line fail and phone line restoral reports when the events occur.
They are also included in Expand Test Report, page 30 initiated from a keypad or by a Skeds,
page 216.
Phone line fail events are assigned to Area 1 and use the Area 1 configuration. For example,
the Area 1 account number is used for reporting.
RPS Menu Location
Panel Wide Parameters > Phone and Phone Parameters > Phone Supervision Time
3.1.5

Alarm on Fail

Default: No
Selections:
Notice!
UL 864 requirement for commercial fire
To comply with UL864 requirements for commercial fire systems, set this parameter to No.
To use this Alarm on fail feature, enable phone line supervision at the  Phone Supervision Time,
page 29 parameter.
The alarm response for phone line fail events includes:
Bosch Security Systems, Inc.
Yes - the control panel dials phone numbers using DTMF (dual-tone multi-frequency,
touch-tone).
No - the control panel dials phone numbers using pulse dialing.
0 - disabled, no phone line supervision.
10-240 (seconds) - number of seconds (in 10 second increments) a phone line must be
faulted before the control panel creates a phone line fail event.
Yes - initiate an alarm response for phone line fail events.
No -. initiate an alarm response for phone line fail events
activating the Area 1 Burglar Bell,
Program Entry Guide
Panel Wide Parameters | en
2017.03 | 09 | F.01U.303.998
29