en | Panel Wide Parameters
The control panel readjusts the heartbeat poll rate temporarily from less than 300 seconds to
300 seconds when online with RPS. The poll rate returns to the programmed value after the
RPS session ends.
RPS Menu Location
Panel Wide Parameters > Enhanced Communications > Poll Rate
3.11.6

ACK Wait Time (sec.)

Default: 0 (Receiver Supervision Time parameter set to Custom)
Selections: 5 to 65535 (seconds)
Notice!
Receiver Supervision Time, page 63 parameter must be set to Custom
to edit Poll Rate (sec.), page 64, ACK Wait Time (sec.), page 66 and Retry Count, page 66
parameters
With the exception of the Custom selection, the Receiver Supervision Time parameter
automatically sets the Poll Rate, ACK Wait Time, and Retry Count parameters. These
parameters can only be edited when the Receiver Supervision Time parameter is set to
Custom.
The first time Custom is selected, the default value for the Poll Rate, ACK Wait and Retry
Count parameters is zero. Once these parameters are changed from the default, RPS retains
the values even if the Receiver Supervision Time parameter is changed from the Custom
selection. Each time Custom is reselected the Poll Rate, ACK Wait and Retry Count
parameters are reset to the saved values.
This parameter determines how long the control panel will wait for an acknowledgement from
the central station after a heartbeat poll or an actual event has been transmitted.  Actual (non-
heartbeat) events will wait the set value or a maximum of 15 seconds before the next
communication attempt is made.
RPS Menu Location
Panel Wide Parameters > Enhanced Communications > ACK Wait Time
3.11.7

Retry Count

Default: 0 (Receiver Supervision Time parameter set to Custom)
Selections:
 0 - continuous retries. Path failure events are not generated.
1 to 255 - path failure events are generated after the number of retries are reached.
Notice!
Receiver Supervision Time, page 63 parameter must be set to Custom
to edit Poll Rate (sec.), page 64, ACK Wait Time (sec.), page 66 and Retry Count, page 66
parameters
With the exception of the Custom selection, the Receiver Supervision Time parameter
automatically sets the Poll Rate, ACK Wait Time, and Retry Count parameters. These
parameters can only be edited when the Receiver Supervision Time parameter is set to
Custom.
The first time Custom is selected, the default value for the Poll Rate, ACK Wait and Retry
Count parameters is zero. Once these parameters are changed from the default, RPS retains
the values even if the Receiver Supervision Time parameter is changed from the Custom
selection. Each time Custom is reselected the Poll Rate, ACK Wait and Retry Count
parameters are reset to the saved values.
2017.03 | 09 | F.01U.303.998
Program Entry Guide
Control Panel
Bosch Security Systems, Inc.