114 en | Keypads
This parameter defines a single purpose to this keypad; however entry of a passcode with
authority in the current area will always silence alarms and troubles.
When a Passcode Enter Function is unable to be executed due to configuration conflicts, then
the control panel performs the Arm/Disarm function regardless of setting.
The Service Passcode (User ID 0) cannot be used to operate the Passcode Enter Functions.
Outputs used for the Cycle Output function must not be shared with any other point, sensor
reset, control panel, or bell functions. Sharing can cause errors in output operation.
Notice!
To comply with SIA CP-01 False Alarm Reduction, keep this parameter at its default setting.
RPS Menu Location
Keypads > Keypad Assignments > Passcode Enter Function
5.1.11

Dual Authentication

Default: No
Selections:
This parameter sets the requirement that a user must present any two forms of authorization
(passcode at a keypad, or credential or keyfob to a door reader) in order to gain access.
Before setting this parameter to YES, first Assign Door, page 114 or Keypad Type, page 110.
 If the keypad is a B94X Touch Screen and the Assign Door prompt is set to No Door, then the
keypad reader is used for Dual Authentication.
If the keypad is a B94X Touch Screen and the Assign Door prompt is set to Door #, then the
keypad reader is disabled and the door reader is used for Dual Authentication.
RPS Menu Location
Keypads > Keypad Assignments > Dual Authentication
5.1.12

Dual Authentication Duration

Default: 20 Seconds
Selections: 10, 15, 20, 25, 30, 35, 40, 45 seconds
This parameter sets the time out between the presentation of the first and second form of
authorization (passcode, credential or keyfob).
RPS Menu Location
Keypads > Keypad Assignments > Dual Authentication Duration
5.1.13

Assign Door

Default: No Door
Selections: No Door, Door 1 to Door 32 (Door 1 to Door 8 for B8512)
Notice!
The B9512 supports up to 32 keypads on an SDI2 bus, or up to 16 on an SDI bus. The
B8512G supports up to 16 keypads.
2017.03 | 09 | F.01U.303.998
No Door: No door controller is assigned for adding tokens or the CLOSE DOOR # display
on the keypad.
1 – 32 (1 – 8 for B8512): Assign the door controller that enters the Add User? mode when
initiated. This door activates the CLOSE DOOR # display at this keypad if Close Door is
set to Yes.