en | Panel Wide Parameters
3.3.5

Reporting Delay for No Towers (sec.)

Notice!
Important configuration information for cellular communication
Refer to Configuring for Cellular Service, page 280 for an overview and configuration
information.
Default: 0
Selections: 0-3600 (seconds)
When there are no towers present the control panel starts two timers, one for a
No Towers event, one for a No IP Address event. The control panel uses the duration set by
this Reporting Delay for No Tower parameter for both timers. If the cellular plug-in module
does not find a tower before the end of the delay, the control panel creates a No Towers event
and a No IP Address event at the same time.
The control panel creates a No Tower restoral event when one or more towers are available for
the duration set by this Reporting Delay for No Tower parameter.
The contro panel creates a No IP Address restoral event when the cellular plug-in module
successfully registers with one or more towers and receives an IP address.
Notice!
When one or more towers are available, 60 second delay for No IP Address event
If the cellular plug-in module successfully registers with one or more towers, but does not
receive an IP address within 60 seconds, the control panel creates a No IP Address event.
RPS Menu Location
Panel Wide Parameters > Cellular Plug-in Module > Reporting Delay for No Towers
3.3.6

Outgoing SMS Length

Notice!
Important configuration information for cellular communication
Refer to Configuring for Cellular Service, page 280 for an overview and configuration
information.
Default:  160
Selections: 0 to 3600 (bytes)
This parameter sets the maximum length for outgoing messages.
Outgoing SMS messages are rejected if over this length. This maximum length must match the
maximum length set by the cellular provider that is transmitting the SMS message (for
example, Verizon).
RPS Menu Location
Panel Wide Parameters > Cellular Plug-in Module > Outgoing SMS Length
2017.03 | 09 | F.01U.303.998
0 - Disabled.
1 to 3600 - Enabled.
0 - Disabled.
1 to 3600 - Outgoing SMS length (number of bytes)