108 en | Area Wide Parameters
For example if Area Re-Arm Time is set to four hours (04:00) and the area is disarmed (turned
off) at 1:30 pm, it rearms to All On Delay at 5:30 pm. Any points not ready to arm (faulted) are
force armed.
Notice!
Force Arm / Bypass Max is ignored when re-arming
All points not ready to arm (faulted) are force armed when the area re-arms at the end of Area
Re-Arm Time.
The area automatically re-arms at 11:59 pm regardless of when the Area Re-Arm timer started.
For example, if the Area Re-Arm timer is set to 4 hours (04:00) and the area is disarmed
(turned off) at 10:30 pm, the area rearms to All On Delay at 11:59 pm (1 hour and 29 minutes
after disarm).
Users can use Extend Close time from a system keypad to extend an active Area Re-arm delay
(On/Off Menu > Extend Close time).
Notice!
Configuring Closing Window and Area Re-Arm Time may cause unexpected Area behavior.
When both a Closing Window and Area Re-Arm Time are configured for the same area,
the Closing Window is running simultaneously with the Area Re-arm timer,
and a user uses the Extend Close time from a system keypad,
the control panel extends only the Closing Window, not the Area Re-Arm Time.
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Area Re-Arm Time
4.2
Area Arming Text
The B9512G supports up to 32 areas. The B8512G supports up to 8 areas.
4.2.1
Area name text
Default: Area # (# = the Area number)
Selections: Up to 32 characters
This parameter sets what is displayed at keypads. This is for informational purposes only.
Enter up to 32 characters of text, numbers and symbols to describe the area.
–
–
RPS Menu Location
Area Wide Parameters > Area/Bell Parameters, Open/Close Options > Area Arming Text > Area
Name Text
4.2.2
Account is On text
Default: Blank
Selection: Enter up to 32 characters.
This parameter displays the text to display at the keypad for each area as required.
Notice!
When using a D1255F, D1256F, or D1257F keypad, program this parameter as *Fire System*.
2017.03 | 09 | F.01U.303.998
Keypads display the first 20 characters. If more than 20 characters are used, the area
name text scrolls across the display one time. To scroll the text again, press [ESC].
Spaces before, after and within a string of text are treated as text and are included in the
32 character limit.